INSTALLATION OF REFRIGERANT PIPING
Step 6
Piping Connections to Outdoor Unit
1. Remove service valve cover (if provided) to
access the service valves and refrigerant ports.
2. Carefully bend and adjust length of refrigerant
pipes to meet outdoor unit service valves
connections with proper tools to avoid kinks.
NOTE: Use proper techniques to cut and re-flare refrigerant pipes, if required.
An R410A Fla
ring Tool is required for re-flaring refrigerant pipes.
3. Apply a small amount of refrigerant oil to the flare connection on the refrigerant pipe.
4. Properly align piping and tighten flare nut using a standard wrench and a torque
wrench as shown in the indoor piping section.
5. Carefully tighten flare nuts to correct torque level referring to the following Torque Table:
NOTE: Over tightening may da
mage flare connections and cause leaks.
Pipe Diameter Nut Size
Tightening Torque
inch (mm) inch (mm) ft-lbs N-m
1/4 (6.35) 1/4 (17) 10 to 13 14 to 18
3/8 (9.5) 3/8 (22) 25 to 30 34 to 42
1/2 (12.7) 1/2 (25) 36 to 45 49 to 61
5/8 (15.9) 5/8 (29) 50 to 60 68 to 82
Torque Table
Service
Valve Cover
INSTALLATION OF POWER AND WIRING
Step 7
Indoor Unit Interconnecting Wire Connections
Disconnect all electrical power to unit including disconnects,
fuses and circuit breakers.
1. Open front cover of indoor unit and remove field wiring terminal block cover.
2. Pull interconnecting wires up from back of indoor unit and position in close to the
terminal block on indoor unit.
NOTE: The indoor unit is powered from the outdoor unit, depending on local code,
a disconnect switch may need to be installed to a power supply circuit.
3. Connect wiring to indoor unit per connection diagram.
NOTE: Record wire colors and terminal references for uses with Outdoor Unit
wire connections.
4. Replace field wiring cover and close front cover of indoor unit.
WARNING
16
TWD-0813-032 Neo install REV:Layout 1 9/27/13 12:15 PM Page 17